Hot Water Circulation and Additional Flow

論文類型 技術與工程 發表日期 2005-10-01
作者 Sheng,Guorong
關鍵詞 circulating flow additional flow circulating-pump flow circulating-pump head
摘要 By analyzing the process of hot water circulating and the implication of additional flow,the weakness,lying in the definition of additional flow and in the calculation formula of circulating-pump head and circulationg-pump flow in current code,is pointed

Hot Water Circulation and Additional Flow
Sheng Guorong
ChongQing Architectural Design Instiute
Add:No.31 Renhe Street, Yuzhong District, Chongqing Zip Code:400015
Tel:023-63621179 Fax:023-63856935

ABSTRACT By analyzing the process of hot water circulating and the implication of additional flow,the weakness,lying in the definition of additional flow and in the calculation formula of circulating-pump head and circulationg-pump flow in current code,is pointed out. The implication of additional flow is also discussed.A new opinion about calculationg the pump head and the pump flow is brought brought forward.
KEYWORDS circulating flow, additional flow, circulating-pump flow,circulating-pump head
1 Requirements of the code
In curent Code for Design of Building Water Supply and Drainage(GBJ15-88),there are mainly two stipulations to the circulating-pump in a central heating flow,the circulating-pump head should as 15% of the maximum hourly hot-water consumption;Secondly,the circulating-pump head should be counted as Hb=(1+qf/qx)2.hp+hx[formula?],in which Hb is the circulationg-pump head is the circulation flow;qf is the additional flow,hp and hx are the head loss in distributing pipes and in is the circulationg flow;qf is the additional flow,hp and hx are the head loss in distributing pipes and in returning pipes respectively. In the code,the additional flow is definged as follows: In a mechanical circulating hot-water flow should be considered when calculating the head loss in the distributing pipes, so as to prevent the circulation from being destroyed by the partial water consumption. This water flow is called as an additional flow.
In recent years, many queries focusing on the implication and calculation the additional flow are put forward,but this seemed to have taken no effect on the code. In this paper, these queries are to be discussed.
According to the code, the formula for calculating the circulating flow is :qx=(3600Qs)/(C.?t),where Qs is the heat loss,which can be counted as 5%to 10%of the hourly heat consumption;C is the specific heat of water;?t is the temperature difference. It‘s obvious that the circulating flow is figured out on the assumption that there is no consumption occurring in the hot water system, the purpose of circulating is to maintain the temperature of the system.
2. One opinion about the implication of additional flow
According to formula?, when we calculate the circulating-pump head, the head loss in distributiong pipes should be counted as (1+qf/qx)2.hp,this indicates that not only the circulating flows, but also the additional flow passes through the distributing pipes;while, the head loss in returning pipes is still hx, this shows that the additional flow doesn‘t pass through the returning pipes. Inthe definition, it‘s said that the additional flow should be considered "when calculating the head loss in the distributing pipes".Where the distributing pipes are mentined but not are the returning pipes,this also indicates that the additional flow passes through only the distributing pipes but not the returning pipes.So it seems reasonable to think in this way: the additional flow arises from the partial water consumption, and it approximately reflects the small quantity of consumption. As shown in figure1, the flow is replenished by cold water pipe. Since it is an approximate reflection of partial water consumption, certainly it passes(or partially)through the distributing pipes. It‘s also clear that it doesn‘t pass through the returning pipes, because it‘s consumed, it doesn‘t take part in the circulation really, it can‘t be called as an additional circulating flow. From figure 1, it also can be found that the additional flow is supplied from behind the circulating pump but not from before the pump, it doesn‘t pass through the pump. The core of this opinion is that the additional flow passes through only the distributing pipes but neither the returning pipes nor the punmp,which is deduced from the code. But this doesn‘t agree with another part of the code, which requires the pump flow to be the summation of circulating flow and additional flow. Since the additional flow doesn‘t pass through the pump,why must the outflow of the pump be the summation of the circulating flow and the additional flow as described in the code? A contradiction appears.
Somebody says figure 2 can work, because the additional flow passes through both the pump and the distributing pipes but not the retuming pipes, which is in accordance with the code. But that manner is not always feasible in most cases. In that manner, because the pump has to be running all the time and the outflow might range between one-tap-flow and a design flow, it‘s difficult to choose a centrifugal pump to meet the request.
3. Another opinion about the implication of additional flow
According to the code, the additional flow is utilized to prevent the circulation from being destroyed. So it appears logical to think in this way:Because the circulating flow is figured out on the assumption that there is no consumption in the hot water system, it can be called as a "theoretical circulating flow"to which is resorted to make up for the heat loss.When it‘s averaged to several vertical pipes ,the circulating flow in each pipe may be very little. In order to keep the circulation from being destroyd by partial consumption ,an extra flow should be added to the theoretical circulating flow ,thus a "factual circulating flow‘is gained. Because the flow in each pipe is enlarged, the influence of the partial consumption is remarkably reduced. Consequently, the circulation effect is ensured. This extra flow is just the "additional circulating flow".Being understood in this way, the additional flow is not an approximation of the partial consumption but an extra flow added to the theoretical circulating flow.It passes through the pump, the heat exchanger, the distributing pipes and the returning pipes, therefor it takes part in the circulation really and can be called as an additional circulating flow. Since it passes through the returning pipes, certainly the head loss in returning pipes ought to be counted as (1+qf/qx)2.hx but not hx yet.Thecore of this opinion is that the additional flow passes through the entire pipe-loop of the pump should be summation of the circulating flow and the additional flow",but it conflicts with formula(1) in calculating the head loss in returning pipes. This opinion can‘t make the code justify itself none the less.
4 Comparison of the two opinions
The implications of "additional flow"are quite different in above two opinions. According to the former one ,the cold water pipe replenishes the additional flow, and this flow is consumed in the distributing pipes, so it seems more exact to call the flow an "additional distributing flow"(qpf)than to call it an "additional circulating flow".To the latter opinion ,the additional flow does take part in the circulation, it can be called as an " aadditional circulating flow"(qxf).The two different implications are both referred to in the code, but they are not told from each other. If it‘s necessary to keep the circulation from being destroyed and properly figure out the head loss in the pipe-loops,both the two kinds of additional flows ought to be taken into account, namely Hb=[1+(qpf+qxf)/qx]2.hp+(1+qxf/qx)2.hx[formula?].If the factual circulating flow is shown as qsx(namely qsx=qpf+qxf),the head loss in distributing pipes and returning pipes are shown as hsp and hsx respectively, from formula? the following formula is derived; Hb=(1+qpf/qsx)2.hsp+hsx[formula ?].formula?resembles formula ? formally.
5 Examples
In a section of a hotel, the parameters are as follows:n=280beds, q=200l/bed.d, Tr=60?,T1=7?,?t=10? and Kh=5.73, thus Qh=13.4m3/h;If Qs is estimated as 7% of the maximum hourly heat consumption, then qx=5.0m3/h. When qx is averaged to the 10 vertical pipes, the circulating flow in each pipe is 0.5m3/h. As the diameter of inlet and outlet are DN50 and DN25 respectively, the velocities of inlet and outlet are Vi=0.07m/s and Vo=0.28m/s respectively. Considering the qf which is counted as 15% of the Qh according to the code,the total factual circulating flow is enlarged to be 0.7m3/h?then the velocities are Vi=0.10m/s and Vo=0.40m/s.
In a section of a hospital, each original parameter is the same as above except Kh=2.66. Then the results are Qh=6.2m3/h and qx=2.3m3/h, accordingly Vi=0.03m/s and Vo=0.13m/s. Appended with the qf, the velocities are Vi=0.05m/s and Vo=0.18m/s.
From above, it‘s easy to find that in a hotel, no matter the additional flow is considerd or not ,the velocity in each vertical pipe changes little; with the same Qh, the more are the vertical pipes, the more will the velocity decrease. Ina hospital, as the Kh is much smaller than in a hotel, the velocities are much lower even if the additional flow is considered.
6. Factors influencing the effect of circulation
What on earth is the disadvantage of a too low velocity? As we know, although each pipe-loop is designed to be nearly alike, the circulating velocities may be very different ,we have to make them nearly identical by the conditioning of the valves. If the velocities are too low,it will be very difficulty to ensure a certain quantity of flow passing through the pipes and avoid any short-circuiting. Unfortunately, from above example of a hospital, we can see that even if the additional flow is considered according to the code,the disadvantage is not avoided. That means the destruction of circulation can‘t avoided.
If the circulating velocity is not very low, will the partial water consumption destroy the circulation ? Let‘s analyze it referring to figure 1. If there‘s a consumption near the inlet of a vertical pipe(as at point A),because the pipe diameter is relatively big enough ,the circulating flow in this pipe won‘t be influenced remarkable, the circulation of the whole pipes is not destroyed .If the consumption is near the outlet of the pipe(as at point B), because the pipe diameter is relatively small,the circulating flow in this pipe will must decrease and the circulation of the pipe seems destroyed. But the total flow of the pipe increases,the heat loss is compensated for, the "destruction"doesn‘t matter; and the circulating flows in other pipes increase a little. In the same way ,if the consumption is at the middle of the pipe(as at point C),the total flow during point A and point C increases, and the total flow (circulating flow )during point C and point B decreases a little. It is clear that the nearer is the consumption point to the inlet ,the less is the influence to the circulation; the nearer is it to the outlet, the shorter is the influenced pipe.
Above analysis shows: although the partial consumption may reduce the circulating flow in a vertical pipe, the total flow of the pipe won‘t decrease. So the heat loss can be compensated for, the destruction doesn‘t harm the purpose of circulation. The more is the consumption, the better is the circulation effect. So long as the circulation can be ensured with no partial consumption, even if the partial consumption occurs, the effect of circulation can be ensured all the same. What really matters is how to ensure the circulation with no consideration of the partial consumption.
7 Conclusions
The additional flow is just adopted to ensure an appropriate factual circulating flow so that the circulation can be ensured; therefor the determination of an additional flow is of significant sense.From my point of view, when we determine the outflow of a circulating pump,the theoretical circulating flow should be figured out first according to the code,then the circulating velocity of each pipe must be verified. If it‘s not very low, the additional flow needn‘t be considered. Otherwise, if it‘s too low, the additional flow should be added to the circulating flow, thus we can get a factual circulating flow that can be the outflow of the pump. the pump head needn‘t be counted as formula?. So an appropriate circulating velocity determines the additional flow. What velocity can be regarded as an appropriate one? This depends. As in above example of a hotel, the outlet velocity of 0.3m/s or so (counted according to the code)is acceptable; it‘s also proved feasible by many other practical projects. But it‘s not the case in a hospital, the additional flow should be determined according to an appropriate velocity(for instance, 0.3m/s) but not to the code.
All in a word, the circulating velocity determines if an additional flow should be taken into account; and the quantity of the additional flow should also be determined by nthe verification of the velocity so as to get an appropriate factual circulating flow. Only in this way can the effect of circulation be ensured.


論文搜索

發表時間

月熱點論文

論文投稿

很多時候您的文章總是無緣變成鉛字。研究做到關鍵時,試驗有了起色時,是不是想和同行探討一下,工作中有了心得,您是不是很想與人分享,那么不要只是默默工作了,寫下來吧!投稿時,請以附件形式發至 paper@h2o-china.com ,請注明論文投稿。一旦采用,我們會為您增加100枚金幣。

国产黄大片在线观看画质优化| 久操视频在线| 黄色日韩网站| 欧美激情亚洲综合一区| 成人国产精品免费视频| av资源网在线观看| 日本sm残虐另类| 中文综合在线观看| av手机免费观看| 日韩免费在线| 欧美精品一区二区三| 成人综合av网| 四虎最新网站| 天天久久夜夜| 日韩欧美国产一区二区三区 | 亚洲一二三区在线| 欧美xxxxxxxxx59| 一区二区三区中文在线观看| 亚洲精品欧美专区| 日韩精品黄色网| 国产91aaa| 日韩免费一级视频| 国产精品15p| 欧美人与z0zoxxxx视频| 97久久国产亚洲精品超碰热| 黄色av网址在线播放| 91精品电影| 久久青草福利网站| www.8ⅹ8ⅹ羞羞漫画在线看| 亚洲成年人网站在线观看| www.浪潮av.com| 激情综合网最新| 国产视频一区二区三区四区| 日韩av午夜| 亚洲天堂精品视频| 亚洲永久激情精品| 日韩毛片免费看| 亚洲一卡二卡三卡四卡| 日韩高清三级| 999精品视频在这里| 在线视频国内自拍亚洲视频| 日产精品高清视频免费| 国产 日韩 欧美 综合 一区| 一区av在线播放| 91九色蝌蚪嫩草| 91精品国产综合久久香蕉的特点| 在线播放日韩导航| 欧美成人video| 亚洲性69xxxbbb| 美日韩精品视频免费看| 97涩涩爰在线观看亚洲| 国产精品观看在线亚洲人成网| 成人信息集中地欧美| 成人免费在线一区二区三区| 日韩不卡av| 欧美一级免费播放| 在线观看成人影院| 日韩成人黄色| 国产深夜视频在线观看| 四虎永久精品在线| 久久99青青| 中日韩视频在线观看| 国产一区二区三区免费看| caoporen国产精品视频| 亚洲三级在线播放| 日本二三区不卡| 欧美精品一区二区三区蜜桃| 久久中文字幕在线| 国产精品久久久久影院日本 | 久久成人av网站| 国产激情综合五月久久| 国产精品区一区| 人妻无码一区二区三区四区| 国产主播中文字幕| 男人的天堂在线| 交100部在线观看| 九九热播视频在线精品6| 狠狠综合久久| 白白色 亚洲乱淫| 亚洲一区二区3| 精品不卡在线视频| 亚州欧美日韩中文视频| 国内精品视频在线播放| 自拍日韩亚洲一区在线| 最新版sss视频在线| av中文在线资源库| 巨人精品**| 亚洲专区一区| 久久久久久久久久电影| 午夜久久久影院| 亚洲精品中文字| 日本韩国在线不卡| 午夜精品一区二区在线观看| 欧美日韩一区二区三区69堂| 黄色网在线免费观看| 亚洲成av人片在线观看www| 亚洲第一天堂| 国产成人av电影| 偷拍亚洲欧洲综合| 亚洲午夜性刺激影院| 91久久精品国产91久久| youjizz.com在线观看| 人人在线97| 黄色软件视频在线观看| 欧美日韩第一| 国产精品一区二区久久精品爱涩| 亚洲综合一区二区精品导航| 日韩精品在线观看网站| 国产免费亚洲高清| 妺妺窝人体色777777| 成年午夜在线| 北条麻妃一区二区三区在线观看 | 亚洲国产精品专区久久| 2019中文字幕在线观看| 五月天久久狠狠| 天堂av免费观看| 欧美性suv| 综合视频在线| 91色乱码一区二区三区| 欧美精品久久久久久久久老牛影院| 欧美激情一区二区三级高清视频| 欧美18视频| 爽爽免费视频| 成人精品一区二区三区电影| 伊人久久大香线蕉综合热线| 国产日韩欧美亚洲| 精品va天堂亚洲国产| 成人黄色在线播放| 国产三区在线视频| 性欧美高清come| 日韩欧美精品| 久久亚区不卡日本| 日韩欧美一区在线| 国产日韩精品在线| 欧美成人黑人猛交| yellow91字幕网在线| 欧美精品一区二区三区中文字幕 | 日韩网址在线观看| 丝袜美腿av在线| 久久综合国产| 日本一区二区成人| 亚洲免费av片| 国产一区二区三区无遮挡| 中文字幕桃花岛| 亚洲日本在线观看视频| 久久亚洲二区| 一本一本大道香蕉久在线精品| 久久久久久网址| www.18av.com| 欧美色图天堂| 一区在线观看| 99精品国产视频| 高跟丝袜一区二区三区| 久久综合久中文字幕青草| 日本午夜精品一区二区| 500福利第一精品导航| a一区二区三区亚洲| 久久综合图片| 色综合久久中文字幕| 26uuu另类亚洲欧美日本一| 欧美高清中文字幕| 欧洲一区二区三区| 欧美特黄一区| 夜夜亚洲天天久久| 欧美激情三级免费| 成人在线视频一区二区三区| а√天堂资源地址在线下载| 亚州av乱码久久精品蜜桃| 国产亚洲综合在线| 国产一区二区三区高清在线观看| 欧美日韩免费高清| 丝袜+亚洲+另类+欧美+变态| 日韩在线你懂的| 国产视频在线观看一区二区三区| 亚洲欧洲一区二区三区在线观看 | 亚洲一区二区三区日本久久九| 精品中文字幕一区二区小辣椒| 欧美高清dvd| 国产日韩精品入口| 天堂av免费观看| 嫩草影视亚洲| **网站欧美大片在线观看| 欧美高清视频免费观看| 国产淫片免费看| 欧美黄色网络| 国产成人aaa| 中文字幕成人精品久久不卡| 好色先生视频污| 中文字幕成在线观看| 久久成人综合网| 亚洲福利视频网站| 亚洲黄色成人久久久| 污的网站在线观看| 日韩国产在线观看| 欧美日韩大陆一区二区| 97超碰人人看人人| 超碰免费在线| 国产视频亚洲| 精品国产网站在线观看| 一区二区三区观看|